State of Charge as Related to Specific Gravity and Open Circuit Voltage | ||||||||||||||
Percentage of Charge | Specific Gravity Corrected To | Open-Circuit Voltage | ||||||||||||
6v | 8v | 12v | 24v | 36v | 48v | |||||||||
100 | 1.277 | 6.37 | 8.49 | 12.73 | 25.46 | 38.20 | 50.93 | |||||||
90 | 1.258 | 6.31 | 8.41 | 12.62 | 25.24 | 37.85 | 50.47 | |||||||
80 | 1.238 | 6.25 | 8.33 | 12.50 | 25.00 | 37.49 | 49.99 | |||||||
70 | 1.217 | 6.19 | 8.25 | 12.37 | 24.74 | 37.12 | 49.49 | |||||||
60 | 1.195 | 6.12 | 8.16 | 12.27 | 24.48 | 36.72 | 48.96 | |||||||
50 | 1.172 | 6.02 | 8.07 | 12.10 | 24.20 | 36.31 | 48.41 | |||||||
40 | 1.148 | 5.98 | 7.97 | 11.89 | 23.92 | 35.87 | 47.83 | |||||||
30 | 1.124 | 5.91 | 7.88 | 11.81 | 23.63 | 35.44 | 47.26 | |||||||
20 | 1.098 | 5.83 | 7.77 | 11.66 | 23.32 | 34.97 | 46.63 | |||||||
10 | 1.073 | 5.75 | 7.67 | 11.51 | 23.02 | 34.52 | 46.03 |
Table 2 | |||||
Charger Voltage Settings for Flooded Batteries | System Voltage | ||||
Charger Voltage Setting | 6v | 12v | 24v | 36v | 48v |
Bulk Charge | 7.4 | 14.8 | 29.6 | 44.5 | 59.3 |
Float Charge | 6.7 | 13.5 | 27 | 40.5 | 54 |
Equalize Charge | 8.1 | 16.2 | 32.4 | 48.6 | 64.8 |
Table 3 | ||||
Charger Voltage Settings for VRLA Batteries | System Voltage | |||
Charger Voltage Setting | 12v | 24v | 36v | 48v |
Bulk Charge | 14.4 | 28.8 | 43.2 | 57.6 |
Float Charge | 13.5 | 27 | 40.5 | 54 |
FOR SOLAR APPLICATION
System Voltage | |||||
Voltage Settings | 6V | 12V | 24V | 36V | 48V |
Daily Charge | 7.4 | 14.8 | 29.6 | 44.5 | 59.3 |
Float Charge | 6.7 | 13.5 | 27 | 40.5 | 54 |
Equalize Charge | 8.1 | 16.2 | 32.4 | 48.6 | 64.8 |